ABB FBIP-21 BACnet/IP User Manual page 43

Adapter module
Table of Contents

Advertisement

Object
Default object name
ID
AV54
LOOP-1-Integration-
Time
AV55
LOOP-2-Feedback-
Monitor
AV56
LOOP-2-Setpoint-
Monitor
AV59
LOOP-2-Output
AV60
LOOP-2-Gain
AV61
LOOP-2-Integration-
Time
AV64
LOOP-2-Deviation-
Monitor
AV130
Kilowatt-Hour-This-
Hour
AV131
Kilowatt-Hour-Last-
Hour
AV132
Kilowatt-Hour-This
Day
AV133
Kilowatt-Hour-Last-
Day
Description
Loop-1 integration time
External loop controller feed-
back value after source selec-
tion, mathematical function
and filtering (read-only)
External loop controller set-
point value after source selec-
tion, mathematical function
limitation and ramping (read-
only)
External loop controller out-
put
External loop controller gain
External loop controller integ-
ration time
External loop controller devi-
ation
Kilowatt hour this hour
Kilowat hour during last hour
Kilowatt hour today
Kilowatt hour last day
Communication protocol 43
Minimum/ Maxim-
Unit
um present value
(information, de-
pends on the drive
parameter)
0, 3600
s
0, 100
%
0, 100
%
0, 100
%
0.1, 100
No
unit
0, 3600
s
0, 100
%
0, 3.40282347e38
kWh
0, 3.40282347e38
kWh
0, 3.40282347e38
kWh
0, 3.40282347e38
kWh
Present
value ac-
cess type
W
R
R
R
W
W
R
R
R
R
R