Honeywell ACM 150 Manual To Installation, Operation, And Maintenance page 30

Air composition monitor
Table of Contents

Advertisement

 
ACM 150
The output relays are provided for interface to PLCs, for direct activation or alarm
devices and/or for direct initiation of automatic gas shutdown. They may also be
wired to status panels. All relays are double-pole double-throw (DPDT) with dry
contacts rated for maximum 30 VDC, 2 A.
Figure 16. Relay schematic
Relay shown in normal position - (Deenergized with no alarm present).
This diagram is typical of all 86 relays.
Relay number 81 (Power Fail) and relay number 82 (Watchdog) are inverted -
power is always on and drops upon a trouble condition.
Relays number 1 to 80 are programmed by software, relays number 81 through
86 are fixed in function.
See
Programmable relays
 
for additional information on programming.
30