Code
Monitoring signal
V2.19 Temperature input 2
V2.20 Temperature input 3
V3.1
Drive status word
V3.2
Application status word
Table 24. Monitoring values
Unit
ID
51
Measured value of Temperature input 2 in
temperature unit (Celsius or Kelvins) by parameter
setting, hidden until an option board is connected
52
Measured value of Temperature input 3 in
temperature unit (Celsius or Kelvins) by parameter
setting, hidden until an option board is connected
43
Bit codes status of drive
B0 = Ready
B1 = Run
B2 = Reverse
B3 = Fault
B6 = RunEnable
B7 = AlarmActive
B12 = RunRequest
B13 = MotorRegulatorActive
89
Bit codes status of application:
B3 = Ramp 2 Active
B5 = Remote CTRL Place 1 active
B6 = Remote CTRL Place 2 active
B7 = Fieldbus Control Active
B8 = Local Control Active
B9 = PC Control Active
B10 = Preset Frequencies Active