P18.3 Fire mode
frequency
preset
P18.4 Fire mode
activation
close
P18.5 Fire mode
activation
open
Table 42. Fire mode. (Continued)
Min Max Unit Default
P3.1 P3.2
Hz
8.00
0
Varies
6
0
Varies
0
ID
1598 Fire mode frequency preset
NOTE!
This parameter will be locked when
password for fire mode is activated (not in the
test mode), and not only when fire mode input
is set. To change the parameter you have to
disable fire mode.
1619 Digital input, if fire mode is enable or in test
mode then when digital input is closed, fire
mode will be active.
As parameter 5.1
NOTE!
This parameter will be locked when
password for fire mode is activated (not in the
test mode), and not only when fire mode input
is set. To change the parameter you have to
disable fire mode.
1596 Digital input, if fire mode is enable or in test
mode then when digital input is open, fire
mode will be active.
As parameter 5.1
NOTE!
This parameter will be locked when
password for fire mode is activated (not in the
test mode), and not only when fire mode input
is set. To change the parameter you have to
disable fire mode.