Low overload
Low overload = 150% starting torque, 2 sec/20
sec, 110% overloadability, 1 min/10 min
Following continuous operation at rated output
current, 110% rated output current (IL) for 1 min,
followed by a period of load current less than
rated current, and of such duration that the r.m.s
output current, over the duty cycle, does not
exceed rated output current (IL)
High overload
High overload = 200% starting torque, 2 sec/20
sec, 150% overloadability, 1 min/10 min
Following continuous operation at rated output
current, 150 % rated output current (IH) for 1
min, followed by a period of load current less than
rated current, and of such duration that the r.m.s
output current, over the duty cycle, does not
exceed rated output current (IH)