Stripping lengths of motor
and mains cables
Earth con ductor
8 mm
35 mm
Fig. 35. Stripping of cables
NOTE: Strip also the plastic cover of the cables
for 360 degree earthing. See Figures
"SmartVFD HVAC2 power connections,
MI1" on page 24, "SmartVFD HVAC2
power connections, MI2 - MI3" on
page 24 and "Install the control cables.
MI1 - MI3. See Chapter "Control I / O" on
page 53" on page 28.
8 mm
20 mm
38
Cable installation and the UL
standards
To meet the UL (Underwriters Laboratories)
regulations, a UL-approved copper cable with a
minimum heat-resistance of 140/167 °F
(60/75 °C) must be used.
Use Class 1 wire only.
The units are suitable for use on a circuit capable
of delivering not more than 50,000 rms
symmetrical amperes, 600V maximum, when
protected by T and J Class fuses.
Integral solid state short circuit protection does
not provide branch circuit protection. Branch
circuit protection must be provided in accordance
with the National Electric Code and any
additional local codes. Branch circuit protection
provided by fuses only.
Motor overload protection provided at 110% of
full load current.