Digital outputs (Control panel:
Menu PAR -> P7)
RO1 signal selection
RO2 signal selcetion
DO1 signal selcetion
Table 55. Output signals via RO1, RO2 and DO1
Setting
0 =
Not used
Output is not in operation.
1 =
Ready
The frequency converter is
ready to operate.
2 =
Run
The frequency converter
operates (motor is running).
3 =
Fault
A fault trip has occurred.
4 =
Fault inverted A fault trip has not occurred.
5 =
Warning
A warning is active.
6 =
Reversed
The reverse command has
been selected, output
frequency to the motor is
negative.
Signal content
154
Table 55. Output signals via RO1, RO2 and DO1
Setting
7 =
At speed
The output frequency has
reached the set reference.
8
Motor regulator
=
Each of Motor regulator is
active
active (e.g., over current
regulator, over voltage
regulator, under voltage
regulator, etc.)
9 =
FB Control
Output can be controlled with
Word.B13
B13 in the fieldbus control
word.
10 =
FB Control
Output can be controlled with
Word.B14
B14 in the fieldbus control
word.
11 =
FB Control
Output can be controlled with
Word.B15
B15 in the fieldbus control
word.
12 =
Output
Output frequency is over /
frequency superv.
under the limits, set with
parameters P11.1 and P11.2.
13 =
Output
Motor torque is over/under the
torque superv.
limit, se t with parameter P11.3
and P11.4
Signal content
31-00108—07