Honeywell SmartVFD HVAC2 Applications Manual page 182

Table of Contents

Advertisement

Motor
Output voltage
connection
Output current
Starting current /
torque
Output frequency
Frequency resolution 0,01 Hz
Control
Digital input
connection
Analogue input
voltage
Analogue input
current
Analogue output
Digital output
Relay output
Auxiliary voltage
Table 62. SmartVFD HVAC2 technical data. (Continued)
0 - U
Continuous rated current I
+50 ºC (depends on the unit size), overload
1.5 x I
1 min / 10 min
Current 2 x I
depends on motor
0...320 Hz
Positive, Logic1: 18...+30V, Logic0: 0...5V; Negative, Logic1:
0...10V, Logic0: 18...30V; Ri = 10KΩ (floating)
0....+10V,Ri = 250KΩ
0(4)...20mA, Ri ≤ 250Ω
0...10V, RL ≥ 1KΩ; 0(4)...20mA,RL ≤ 500Ω, Selectable through
microswitch
Open collector, max. load 35V/50mA (floating)
Switching load: 250Vac/3A, 24V DC 3A
±20%,max.load 50mA
in
max
N
for 2 sec in every 20 sec period. Torque
N
182
at ambient temperature max.
N
31-00108—07