Download Print this page

Honeywell 2MLL-PMEC User Manual page 16

Profibus-dp(pnet) module, honeywell process solutions

Advertisement

Chapter 2 Specifications
2.1 General Specifications
General specifications of ML200 series are as specified below in Table 2.1.
No.
Items
1
Ambient Temp.
2
Storage Temp.
3
Ambient humidity
4
Storage humidity
5
Vibration Immunity
6
Shocks Immunity
7
Noise Immunity
Operation
8
ambience
9
Altitude
10
Pollution degree
11
Cooling method
Note
1) IEC (International Electrotechnical Commission):
An international nongovernmental organization which promotes internationally cooperated standardization in
electric/electronic field, publishes international standards and manages applicable estimation system related with.
2) Pollution degree:
An index indicating pollution degree of the operating environment which decides insulation performance of the devices.
For instance, Pollution degree 2 indicates the state generally that only non-conductive pollution occurs. However, this
state contains temporary conduction due to dew produced.
1
Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User's Guide
5 ~ 95%RH (Non-condensing)
5 ~ 95%RH (Non-condensing)
Occasional vibration
Frequency
Acceleration
5≤f< 8.4 ㎐
8.4≤f≤150 ㎐
Continuous vibration
Frequency
Acceleration
5≤f< 8.4 ㎐
8.4≤f≤150 ㎐
4.9 ㎨(0.5G)
 Peak acceleration : 147 m/s
 Duration : 11ms
 Pulse wave type : Half-sine (3 times each direction per each axis)
Square wave
impulse noise
Electrostatic
discharge
Radiated
electromagnetic
field noise
Classific
Fast transient
ation
/Burst noise
Voltage
Free from corrosive gases and excessive dust
Table 2.1 General Specifications
Honeywell
Specification
0 ~ 55 C
25 ~ 70 C
Pulse width
-
3.5mm
9.8 ㎨(1G)
-
Pulse width
-
1.75mm
-
2
(15G)
AC : ±1,500V
DC : ±900V
Voltage: 4kV (Contact discharge)
80 ~ 1000 MHz, 10V/m
Power
Digital/Analog Input/Output,
supply
Communication Interface
2kV
Less than 2,000m
Less than 2
Air-cooling
Chapter 2 Specifications
Reference
-
Times
10 times
each
IEC61131-2
direction (X,Y
and Z)
IEC61131-2
LSIS internal
test spec.
IEC61131-2
IEC61000-4-2
IEC61131-2,
IEC61000-4-3
IEC61131-2
IEC61000-4-4
1kV
January 2019
R240

Advertisement

loading

This manual is also suitable for:

2mll-pmea2mll-psea2mll-pmeb2mll-psra