Tools Required; Figure 5-45-5: Part Number And Date Code (D/C) Label On Bottom Of Terminal Pcba Assembly - Honeywell SmartLine SLG 700 User Manual

Level transmitter guided wave radar
Hide thumbs Also See for SmartLine SLG 700:
Table of Contents

Advertisement

Tools required.

Use this tool
AF 2.0 mm Allen key
AF 1.5 mm Allen key
Parker Super O-ring Lubricant
or equivalent
1. Determine transmitter Firmware version of the Sensor and Communications Modules
Sensor Firmware Version
1.000000/1.000100
,
1.010000
1.020000
Figure 5-45-5: Part Number and Date Code (D/C) label on bottom of Terminal PCBA
Page 134
WARNING: When installed as explosion-proof or flame-proof in a
hazardous location, keep covers tight while the transmitter is energized.
Disconnect power to the transmitter in the non-hazardous area prior to
removing end caps for service. When installed as non-incendive or
non-sparking equipment, disconnect power to the transmitter in the
non-hazardous area, or determine that the location is non-hazardous
before disconnecting or connecting the transmitter wires.
For this item
M4 set screw for Separating Sensor Electronics
Housing from Process Connector and
Communications Housing
M3 set screw for end cap removal
Transmitter re-assembly
, and 2.000100
SLG 700 SmartLine Level Transmitter User's Manual
Notes:
COMM PCBA and ADVANCED DISPLAY
must be replaced or have firmware
upgraded.
TERM PCBA must be replaced if the
version number in the date code is not 'C'.
An example of a correct date code is shown
in
Figure 5-45-5
Sensor electronics is replaceable
Revision 8

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents