<Return>
Active Diags (R)
Supply Voltage (R)
Elec Module Temp
(R)
DAC Temp Comp
(R) (HART only)
Sensor Comm (R)
Non-Crit Diag
Display Setup (R)
(HART only)
Characterized (R)
Charact. Status(R)
PV Range (R)
Sensor Over Temp
(R)
Page 116
# #
OK
LOW
HIGH
OK
OVERTEMP
OK
NO
COMPENSATION
OK
SUSPECT
OK
NVM Corrupt
Yes
No
OK
FAULT
OK
Out Of Range
OK
OVER TEMP
SLG 700 SmartLine Level Transmitter User's Manual
Shows the number of Non-Critical
Diagnostics that are currently active
LOW: Supply voltage is below the low
specification limit
HIGH: Supply voltage is above the high
specification limit.
OVERTEMP: Electronics temperature is
outside the operating range (-40°C to +85°C).
The DAC has not been compensated for
temperature effects. This is a factory
operation.
SUSPECT: The interface between the
Temperature Sensor Module and the
Electronics Module is experiencing
intermittent communication failures.
NVM Corrupt: The Display memory is
corrupt.
Yes: Sensor is Characterized
No: Sensor is not Characterized
OK: Characterization table CRC is OK
FAULT: Sensor Characterization data is
corrupted.
When this fault occurred, Sensor Module
fault of Critical Diagnostic will be set.
Out of Range: PV is not within the range
limits
OVERTEMP: Sensor temperature is greater
than 125°C.
Revision 8