Honeywell SmartLine SLG 700 User Manual page 172

Level transmitter guided wave radar
Hide thumbs Also See for SmartLine SLG 700:
Table of Contents

Advertisement

Non-Critical Diagnostics
(Warning Conditions)
Active Diags
Supply Voltage
Elec Module Temp
PV Range
Sensor Over Temp
Prod Sgnl Str
Prod Sgnl Qlty
Upper Product Signal Strength
Upper Product Signal Quality
Lower Product Signal Strength
Lower Product Signal Quality
Blk Dist Hi Zone
Blk Dist Lo Zone
Page 156
Description
Displays a numeric value of the current
count of non-critical status bits that
have been set.
Displays a status of the power voltage.
Displays a status of the sensor
electronics.
Displays a status of the Loop PV is
within or outside the configured URV
and LRV.
Displays a status of the temperature of
the sensor electronics.
Displays a status of the quality of the
signal strength.
Displays a status of the quality of the
signal.
Displays the status of the strength of
the signal monitoring the upper
product.
Displays the status of the quality of the
signal monitoring the upper product.
Displays the status of the strength of
the signal monitoring the lower product.
Displays the status of the quality of the
signal monitoring the upper product.
Bulk Distance High Zone
The distance within the upper blocking
range.
Bulk Distance Low Zone
The distance within the lower blocking
range.
SLG 700 SmartLine Level Transmitter User's Manual
Resolution
N/A
Ensure the voltage on the
terminals are within
operational specifications.
Bring the sensor within range
and reset the power.
PV Out of Range
Any of the following
conditions can cause this
failure:
1.
Sensor Overload or Fault
or Redundant
Characterization
Calculation Error.
2.
Check range and, where
required, replace
transmitter with one that
has a wider range.
Sensor may have been
damaged.
3.
Check the transmitter for
accuracy and linearity.
4.
Replace the sensor and
recalibrate, where
required.
If the temperature is outside
the configured range, bring
the temperature within the
range and reset or repower.
Read the echo curve and
configure the algorithm and
the dielectric constant.
Theses parameters display
physical locations within the
container where
measurements are not
accurate.
Revision 8