Probe Length
Step
Thread the nut onto the central conductor of the process connector. Refer to
Figure 3-10: SLG726 flanged process connection, probe nut installation
position, mm [in] for nut position on flanged process connectors. Place a lock
washer between the locknut and the first rod segment. Torque the nut against
1
the rod segment and lock washer to secure the connection.
Note: Tighten rod connection point to the following torque:
SLG726 15Nm (11ft-lbs)
Slip the coaxial outer tube over the rod and tighten to the process connector.
Note: Tighten connection point to the following torque:
2
SLG726 30Nm (22ft-lbs)
It is recommended that a process compatible thread locking compound (i.e.
Loctite 242) be used on the outer conductor threaded joints.
Install end spacer between central conductor and outer tube in the
3
counterbore. Secure end spacer using the retaining ring.
Probe Length
Step
Thread the nut onto the central conductor of the process connector. Refer to
Figure 3-10: SLG726 flanged process connection, probe nut installation
position, mm [in] for nut position on flanged process connectors. Place a lock
washer between the locknut and the first rod segment. Torque the nut against
1
the rod segment and lock washer to secure the connection.
Note: Tighten rod connection point to the following torque:
SLG726 15Nm (11ft-lbs)
Slip the "starter" coaxial outer tube over the rod and secure to the process
connection using the M40x1 thread.
Note: Tighten connection point to the following torque:
2
SLG726 30Nm (22ft-lbs)
It is recommended that a process compatible thread locking compound (i.e.
Loctite 242) be used on the outer conductor threaded joints.
Prior to securing the next rod segment, place a "star shaped" spacer over the
3
rod segment end. The wrench flats on the rod end will index the spacer.
Depending on the probe length there could be 0 to 2 more rod segments and 1
rod "end" segment to assemble. Connect the subsequent rod segment to first,
using a stud and lock washer.
4
Note: Tighten rod connection point to the following torque:
SLG726 15Nm (11ft-lbs)
Slip a coaxial coupler over the last rod segment and spacer and tighten onto
the previous outer tube segment.
Note: Tighten connection point to the following torque:
5
SLG726 30Nm (22ft-lbs)
It is recommended that a process compatible thread locking compound (i.e.
Loctite 242) be used on the outer conductor threaded joints.
Revision 8
≤ 2.0m
> 2.0m
SLG 700 SmartLine Level Transmitter User's Manual