Alarm Procedures
2.7.28 BKUPMEMP
The Primary Nonvolatile Backup Memory Failure alarm refers to a problem with the ONS 15310-MA
SDH or CTX 25000 flash memory. The alarm occurs when the ONS 15310-MA SDH has one of four
problems:
The BKUPMEMP alarm can also cause the
by BKUPMEMP, complete the following procedure to clear the BKUPMEMP and the EQPT alarms.
Clear the BKUPMEMP Alarm
Verify that the controller card (ONS 15310-MA SDH) is powered and enabled by confirming a lighted
Step 1
ACT LED on front of the system.
Complete the
Step 2
Wait ten minutes to verify that the card you reset completely reboots. The ACT LED should be green.
If the ONS 15310-MA SDH does not reboot successfully, or the alarm has not cleared, call Cisco TAC
Step 3
(1-800-553-2447).
2.7.29 BLSROSYNC
The BLSROSYNC alarm is not used in the ONS 15310 platforms in this release. It is reserved for
development.
Cisco ONS 15310-MA SDH Troubleshooting Guide, Release 9.0
2-32
Default Severity: Critical (CR), Service-Affecting (SA)
SDH Logical Object: EQPT
Flash manager fails to format a flash partition.
Flash manager fails to write a file to a flash partition.
Problem at the driver level.
Code volume fails cyclic redundancy checking (CRC, a method to verify for errors in data
transmitted to the ONS 15310-MA SDH).
"Soft- or Hard-Reset a Controller Card" procedure on page
"EQPT" alarm on page
2-53. If the EQPT alarm is caused
Chapter 2
Alarm Troubleshooting
2-152.
78-18663-01