System Status Displays - Honeywell GSMV4G Installation And Setup Manual

Intellipath series 4g gsm communicator
Table of Contents

Advertisement

GSMV4G/GSMVCN4G Installation and Setup Guide

System Status Displays

[S]
5-4
ECP 67 TmPB
Flt
xx 5 ++
OK
1234 67 TmPB Flt
5555 xx 5 ++ OK
12345678 TmPB Flt
5555555x 5 ++ OK
1234567 TmPB Flt
5555555 5 ++ OK
Bat NLd: x.xxV
Bat Ld:
x.xxV
ECP Mode
Displays the zone and system fault status.
Press the [Space] key to go to the next field.
Press the backspace [BS] key to go to the previous field.
4204 Emulation Mode
Displays the zone and system fault status.
Press the [Space] key to go to the next field.
Press the backspace [BS] key to go to the previous field.
Two-4204 Emulation Mode
Displays the zone and system fault status.
Press the [Space] key to go to the next field.
Press the backspace [BS] key to go to the previous field.
Zone Trigger Mode
The status display includes:
Zone input status (1234567) – the numbers 1-7
represent the seven mappings of the zone input, and
follow ADEMCO high-speed format codes:
1 = New Event
5 = Normal
X = Not Enabled
Tm – Tamper status follows high-speed format codes
above.
P – Represents line voltage as follows:
+ = Power line voltage OK
– = Power line voltage bad and reported
V = Power line voltage bad, not reported
(reporting window not expired)
^ = Power voltage restored, not yet reported
B – Represents battery condition as follows:
+ = Battery voltage acceptable
– = Battery voltage below 5.7V ±5%
Flt – Represents radio faults:
OK = Normal ; No fault
G = No network connectivity over GSM; fault
time expired.
g = No network connectivity over GSM; fault time
NOT yet expired.
Battery Voltage Display
The voltage levels of the battery connected to the
communicator can be viewed on the 7720P. The first
line of the display shows the voltage level of the battery
with no load. The second line of the display shows
loaded battery voltage. An asterisk (*) next to the
voltage indicates that this is below the accepted level.
Press the [Space] key to go to the next field.
Press the backspace [BS] key to go to the previous field.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gsmvcn4g

Table of Contents