PROMPTS
secondary account must differ from that of the primary account.
Primary City ID
12
(??)_
Primary CS ID
13
(???)
Primary Sub ID
14
(????)
nd
En. 2
CS Y/N
15
(N)_
nd
2
City ID
16
(??)_
nd
2
CS ID
17
(??)_
nd
2
Sub ID
18
(????)_
Device Address
19
(03)_
UL / ULC
Remote access has not been evaluated by UL or ULC.
Remote Access Y/N
20
_
(N)
Direct Wire
Y/N
21
(N)_
Keypad Address
22
(28)_
Supervision
23
(24 Hours)_
OPTIONS
[01-99]
Enter the 2-digit primary city ID, 01-99 (decimal).
[01-FE]
Enter the 2-digit primary central station ID number, 01-FE (HEX).
[0001-9999]
Enter the 4-digit subscriber account number, 0001-9999 (decimal).
Applicable only if control panel supports Central Station #1 and #2
[Y], [N]
Category Enable reporting for the communicator device (e.g.,
VISTA-128BP, FA1660C).
Used if reporting to a second central station is desired.
If [N], go to Prompt 19: "Device Address."
Enter the 2-digit secondary city ID, 01-99 (decimal).
[01-99]
[01-FE]
Enter the 2-digit second central station's ID number, 01-FE (HEX).
Enter the 4-digit subscriber account number for the second central
station, 0001-9999.
[0001-9999]
In ECP mode, the GSMV4G communicates with the control panel
[01-30]
using the ECP bus. Enter the appropriate ECP device address. For
VISTA-10 and VISTA-20 series control panels, use address 03. For
other control panels, see the their Installation and Setup Guide.
NOTES:
1. When programming the control panel, enable the communicator
(or LRR) output.
2. The device address must be unique from the "Keypad Address"
entered in Prompt 22.
Press [Y] to allow the end user to access their system via a website.
[Y], [N]
Availability of this service is controlled by the dealer via the web-
based programming tool on the AlarmNet Direct website.
Applies only to VISTA-128BP/250BP and FBP Series control panels,
[Y], [N]
and FA1660C and 1700C Series control panels.
If [N], and if Prompt 20: "Remote Access" is disabled, skip to Prompt
23: "Supervision."
Must be
[01-30]
Direct Wire downloading.
NOTES:
1. This address must be programmed as an alpha keypad in the
control panel (Device Programming Mode). If using Remote
Access, the keypad must also be enabled as an AUI (advanced
user interface) keypad. DO NOT connect an actual keypad (or
any other device) assigned to this address.
2. This address must be unique from the "Device Address" entered
in Prompt 19.
The AlarmNet network must hear at least one supervisory message
• 30 Day
from the communicator during this supervision period; otherwise,
• 24 Hour
AlarmNet notifies the central station that a communication failure
• None
has occurred. (If the supervision period is changed after registration,
you must re-register the communicator.)
Press the [space] key to scroll through choices.
UL/ULC: Must be set to 24 hours.
Section 3: Programming the Communicator
DESCRIPTION
programmed
if using either the Remote Access feature or
3-5