GSMV4G/GSMVCN4G Installation and Setup Guide
PROMPTS
16
Direct Wire
Y/N
(N)_
Keypad Address
17
(28)_
Supervision
18
(24 Hours)_
Old Alarm Time
19
10 Minutes_
GSM Flt Time
20
(00 mins)_
Flt Rel ON Y/N
21
(N)_
3-12
4204/
ZONE
OPTIONS
2-4204
TRIG.
[Y], [N]
X
[01-30]
X
• 30 Day
X
X
• 24 Hrs
• None
• 10 Min
X
X
• 15 Min
• 30 Min
• 1 Hr
• 2 Hrs
• 4 Hrs
• 8 Hrs
• 12 Hrs
• 24 Hrs
[00-99]
X
X
[00] = not used
[Y], [N]
X
X
DESCRIPTION
VISTA-128BP/250BP and FBP
Applies only to
Series control panels.
If [N], and if Prompt 15: Remote Access is disabled,
skip to Prompt 18: "Supervision."
This address must be programmed if using either
the Remote Access feature or Direct Wire
downloading.
NOTES:
1. This address must be programmed as an alpha
keypad in the control panel (Device Programming
Mode). If using Remote Access, the keypad must
also be enabled as an AUI (advanced user
interface) keypad. DO NOT connect an actual
keypad (or any other device) assigned to this
address.
2. This address must be unique from the "Device
Address" entered in Prompt 14, and cannot equal
that device address plus 1 (one) if using 2-4204
mode.
The AlarmNet network must hear at least one
supervisory message from the communicator during
this supervision period; otherwise, AlarmNet
notifies the central station that a communication
failure has occurred. (If the supervision period is
changed after registration, you must re-register the
communicator.)
Press the [space] key to scroll through choices.
UL/ULC: Must be set to 24 hours.
Sets how long an undeliverable alarm is retried for
delivery to the central station. If the message is not
validated, it is retried until the old alarm time is
reached or the message is validated.
Press the [space] key to scroll through choices.
UL/ULC: Must be set to 10 minutes.
In the event the communicator detects a
communication path failure, enter the time delay (in
minutes) before the communicator notifies the
control panel with a trouble message (and trips the
Fault Output if used (terminal 11); see next
question). The control panel can then notify the
central station.
UL/ULC: Must be one (01) minute.
If enabled, the fault open collector output is
normally energized to ground, and de-energizes
(open circuit) in the event of a communicator fault.
For conditions that trip the fault relay refer to
Supervision Features in Section 1.
Set to [Y] if fail-safe mode is desired.
See Wiring the Fault Relay in Section 2.
UL/ULC: Must be set to "Y".