Phase Sequence And Transformer Polarity; Phase Current Inputs; Ground And Cbct Inputs - GE 339 Instruction Manual

Motor protection system/motor protection and control
Hide thumbs Also See for 339:
Table of Contents

Advertisement

CHAPTER 2: INSTALLATION

Phase sequence and transformer polarity

Phase current inputs

CAUTION:
CAUTION
CAUTION:
CAUTION

Ground and CBCT inputs

339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
For correct operation of the relay features, the user must follow the instrument
transformer polarities, shown in the Typical Wiring Diagram. Note the solid square
markings shown with all instrument transformer connections. When the connections
adhere to this drawing, the arrow shows the direction of power flow for positive watts and
the positive direction of lagging vars. The phase sequence is user programmable for either
ABC or ACB rotation.
The relay has three (3) channels for phase current inputs, each with an isolating
transformer. There are no internal ground connections on the current inputs. Current
transformers with 30 to 1500 A primaries may be used.
Verify that the relay's nominal input current of 1 A or 5 A matches the secondary rating
of the connected CTs. Unmatched CTs may result in equipment damage or inadequate
protection.
Before working on CTs, they MUST be short circuited.
The 339 has two isolating transformers with separate terminals for the 1A/5A secondary
and the CBCT (50:0.025). Only one ground terminal type can be used at a time. There are no
internal ground connections on the ground current inputs.
The maximum ground CT primary for the 1 A and 5 A taps is 1500 A. Alternatively the
sensitive ground input, 50:0.025, can be used to detect ground current on high resistance
grounded systems.
The ground CT connection can either be a zero sequence (core balance) installation or a
residual connection. Note that only 1 A and 5 A secondary CTs may be used for the residual
connection. A typical residual connection is illustrated below. The zero-sequence
connection is shown in the typical wiring diagram. The zero-sequence connection is
recommended. Unequal saturation of CTs, CT mismatch, size and location of motor,
resistance of the power system, motor core saturation density, etc. may cause false
readings in the residually connected ground fault circuit.
ELECTRICAL INSTALLATION
2–13

Advertisement

Table of Contents
loading

Table of Contents