S1 RELAY SETUP

Event recorder

6–44
The 339 firmware accepts GOOSE messages from UR, F650 and UR Plus. The
interoperability with other manufacturers will be guaranteed in almost all cases, by
implementing the reception side with nested structures (one level of nesting) and all the
standard data types.
GOOSE settings changes will take effect only after the 339 relay is re-booted. One setting is
available to Enable/Disable both Transmission and Reception. It is possible to change
these settings from the Front Panel of the relay.
Figure 10: EnerVista SR3 GOOSE General Settings
The Event Recorder runs continuously, capturing and storing the last 256 events. All events
are stored in a non-volatile memory where the information is maintained for up to 3 days
in case of lost relay control power.
PATH
: SETPOINTS > S1 RELAY SETUP > EVENT RECORDER
PICKUP EVENTS
Range: Disabled, Enabled
Default: Disabled
When set to "Enabled", the event recorder records the events that occur when a
protection element picks up.
DROPOUT EVENTS
Range: Disabled, Enabled
Default: Disabled
When set to "Enabled" the event recorder records the dropout state of a protection
element.
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL