Voltage Sensing - GE 339 Instruction Manual

Motor protection system/motor protection and control
Hide thumbs Also See for 339:
Table of Contents

Advertisement

S2 SYSTEM SETUP

Voltage sensing

6–52
A
B
C
PATH:
SETPOINTS > S2 SYSTEM SETUP > VOLTAGE SENSING
VT CONNECTION
Range: Wye, Delta
Default: Wye
The 339 provides three-phase VT inputs. Select "Wye" connection, if phase-neutral
voltages are wired to the relay VT terminals. Select "Delta" connection, if phase-phase
voltages from Delta VT are connected to the three-phase VT terminals. See the VT
connections per the Typical Wiring Diagram in Chapter 2.
VT SECONDARY
Range: 50 V to 240 V
Default: 120 V
This setting defines the voltage across the VT secondary winding when nominal voltage
is applied to the primary. On a source of 13.8kV line-line voltage, with a VT ratio of
14400:120 V delta connection, the voltage to be entered is "115 V". For a Wye
connection, the voltage to be entered is 115/ √3 = 66 V.
VT RATIO
Range: 1:1 to 300:1
Default: 1:1
This setting defines the VT primary to secondary turns ratio. For a 14400: 120 VT, the
entry would be "120:1" (14400/120 = 120).
PHASE A CT
PHASE B CT
PHASE C CT
E5
D5
E6
D6
E7
D7
1A/5A
COM
1A/5A
COM
1A/5A
COM
1A/5A
PHASE A
PHASE B
PHASE C
CURRENT INPUTS
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: SETPOINTS
E8
D8
COM
GROUND