Physical; Environmental - GE 339 Instruction Manual

Motor protection system/motor protection and control
Hide thumbs Also See for 339:
Table of Contents

Advertisement

SPECIFICATIONS

Physical

Environmental

1–16
TEST
Power Frequency Magnetic
Field Immunity
Voltage Dip & Interruption
Radiated & Conducted
Emissions
Sinusoidal Vibration
Shock & Bump
Ingress Protection
Environmental (Cold)
Environmental (Dry heat)
Relative Humidity Cyclic
Fast Transient Disturbance
SWC Damped Oscillatory
Electrostatic Discharge
DIMENSIONS
Size: ........................................................................... Refer to Chapter 2
Weight: .................................................................... 4.1 kg [9.0 lb]
OPERATING ENVIRONMENT
Ambient temperatures:
Storage/Shipping:
Operating:
Humidity:
Altitude:
Pollution Degree:
Overvoltage Category:
Ingress Protection:
REFERENCE STANDARD
IEC61000-4-8
IEC61000-4-11
CISPR11 /CISPR22/ IEC60255-25
IEC60255-21-1
IEC60255-21-2
IEC60529
IEC60068-2-1
IEC60068-2-2
IEC60068-2-30
IEEE C37.90.1
IEEE C37.90.1
IEEE C37.90.3
o
o
- 40
C to 85
o
o
-40
C to 60
Operating up to 95% (non condensing) @ 55
per IEC60068-2-30 Variant 2, 6 days)
2000 m (max)
II
III
IP40 Front , IP10 Back
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 1: INTRODUCTION
TEST LEVEL
Level 4
0,40,70% dips, 250/300cycle
interrupts
Class A
Class 1
Class 1
IP40 (front) , IP10 (back)
o
-20
C 16 hrs
o
85
C 16hrs
6 day variant 2
4KV CM & DM
2.5KV CM & DM
8KV CD, 15KV AD
C
C
o
C (As

Advertisement

Table of Contents
loading