A3 RECORDS

Learned data recorder

Clear learned data

Clear transient record

Clear event record

4–32
The Learned Data Recorder measures and records up to 250 data record "sets," as
indicated in the Learned Data section above, all from actual motor operation. This data
can be used to evaluate changes/trends over time. Note that learned values are calculated
even when features requiring them are turned off.
Clearing motor data (ACTUAL VALUES > A3 RECORDS > CLEAR LEARNED DATA) resets all
these values to their default settings.
LEARNED DATA REC
Range: #xxxx1 of xx250 in steps of 1
This value indicates the number of learned data records saved to date. Only the latest
250 records can be viewed.
DATE OF RECORD
Range: Month, Day, Year
This value is the date on which the record was saved.
CLEAR LEARNED DATA
No
Range: No, Yes
When set to "Yes," pressing the ENTER key will clear all learned data.
PATH:
ACTUAL VALUES > A3 RECORDS > CLEAR TRANST REC
CLEAR TRANST RECORD
No
Range: No, Yes
When set to "Yes," pressing the ENTER key will clear all transient records.
PATH:
ACTUAL VALUES > A3 RECORDS > CLEAR EVENT REC
CLEAR EVENT RECORD
No
Range: No, Yes
When set to "Yes," pressing the ENTER key will clear all event records.
CHAPTER 4: ACTUAL VALUES