Download Print this page

Toshiba GR-200-5 Instruction Manual page 494

Multi functional protection ied

Advertisement

Settings for extra contact health check (special setting, example #3)
Figure 4.1-51 shows an additional setting example for the 43SW scheme; one of the settings is
made hypothetically. That is, the point "DPSY01_OSL_BO_FLG" is actually chosen for the
setting [DPSY01-OSLBORD]; i.e. BO1-RB is not chosen for this selection. This special example
can issue a select command, which is called "operated by internal select function". The user
does not need to consider the use of a BO circuit for a select command, when there are no BO
circuits available.
Table 4.1-32 Extra setting example for contact health check
Example #3
"DPSY01_OSL_BO_FLG" is not connected to any BO
"DPSY01_FSL_BO_FLG" is not connected to any BO
"DPSY01_OEX_BO_CSF" is connected to "BO3" at IO#1
"DPSY01_FEX_BO_CSF" is connected to "BO4" at IO#1
Local/Remote-end
"
DPSY01_OSL_BO_FLG
(511001 8602011DC6)
Select command
Closing
"
DPSY01_FSL_BO_FLG
(511001 8A02011DC4)
Select command
Open
"
DPSY01_OEX_BO
(511001 8202011DD3)
Operate command
Closing
"
DPSY01_FEX_BO
(511001 8102011DD0)
Operate command
Open
Figure 4.1-51 Contact health check setting and 43SW diagram for example #3
Table 4.1-33 PLC monitoring points (Output signal for event suppression function in DPSY)
Signal Number
511001 3102011001
511001 3102021001
511001 8102011F5F
511001 8102021F5F
Table 4.1-34 PLC monitoring points (Output of select signal in DPSY)
Signal Number
511001 8602011DC6
511001 8602021DC6
511001 8A02011DC4
511001 8A02021DC4
"
"
"
"
"
BO3-RB
(
200B41_8202021113)
"
"
"
BO4-RB
(
200B41_8302031113)
Signal Name
Description
DPSY01_3PH_STATE
DPSY01 3ph_state
DPSY02_3PH_STATE
DPSY02 3ph_state
DPSY01_F_QLT_SPP
Event suppression detected (DPSY01)
DPSY02_F_QLT_SPP
Event suppression detected (DPSY02)
Signal Name
Description
DPSY01_OSL_BO_FLG
DPSY01 select (CLOSE) command for Binary Output.
DPSY02_OSL_BO_FLG
DPSY02 select (CLOSE) command for Binary Output.
DPSY01_FSL_BO_FLG
DPSY01 select (OPEN) command for Binary Output.
DPSY02_FSL_BO_FLG
DPSY02 select (OPEN) command for Binary Output.
- 474 -
Setting for example #3
[DPSY01-OSLBORD] =" DPSY01_OSL_BO_FLG"
[DPSY01-FSLBORD]=" " DPSY01_OSL_BO_FLG"
[DPSY01-OEXBORD]=" 200B418202021113" (BO3-RB)
[DPSY01-OEXBORD]=" 200B418202031113" (BO4-RB)
BIO module
Drivers
SW1 is not driven with
any BO
Physical BOs
are virtualized.
SW2 is not driven with
any BO
SW3 is driven with
BO3 at IO#1
BO3
SW4 is driven with
BO4 at IO#1
BO4
6F2T0207 (0.01)
43SW
Plus (+)
SW 1
Closing
SW 3
command
SW 2
SW 4
Open
command
Minus (−)
GRE200 (5,6)