Download Print this page

Toshiba GR-200-5 Instruction Manual page 277

Multi functional protection ied

Advertisement

Setting
2.22.9
ARCD_MV(Function ID:4A7081)
Setting items
ARC-EN
ARC-NUM
ARC
Check
ARC-SucChk
TARCDSUC
TRESET
TREADY
TSHOT
TSHOT_SUB
TRR
TCCW
Multi
MultiShot-EN
-shot
TD_MS2
TRR_MS2
TD_MS3
TRR_MS3
TD_MS4
TRR_MS4
TD_MS5
TRR_MS5
Coordin
ARCCO-OCEN
ation
CO-OC
ARCCO-EFEN
CO-EF
Test setting(Function ID: 4A7081)
Items
Function Test
SHOTNUM-TEST
Range
Unit
Off / On
- Auto reclose mode in 1CB-system
S1 / S2 / S3 / S4 / S5
- Auto reclose maximum shot number
Off / On
- Autoreclose success checking enable
0.10 - 100.00
s Autoreclose success checking time
0.01 - 300.00
s Autoreclose reset time under CB closed
0.0 - 600.0
s Autoreclose ready check time
0.01 - 300.00
s Autoreclose SHOT dead time
0.01 - 300.00
s Autoreclose sub-SHOT dead time
0.01 - 310.00
s Autoreclose reset time
0.01 - 10.00
s Autoreclose ARC command pulse width
Off / On
- Autoreclose multi shot enable
0.01 - 300.00
s 2nd shot ARC dead time
0.01 - 310.00
s 2nd shot ARC reset time
0.01 - 300.00
s 3rd shot ARC dead time
0.01 - 310.00
s 3rd shot ARC reset time
0.01 - 300.00
s 4th shot ARC dead time
0.01 - 310.00
s 4th shot ARC reset time
0.01 - 300.00
s 5th shot ARC dead time
0.01 - 310.00
s 5th shot ARC reset time
Off / On
- Autoreclose OC enable
0.02 - 150.00
A Autoreclose OC threshold
Off / On
- Autoreclose EF enable
0.02 - 150.00
A Autoreclose EF threshold
Range
Unit
Off / S1 / S2 / S3 / S4 / S5 /
- ARC test shot number
S6
- 257 -
Contents
Contents
6F2T0207 (0.01)
Default
Note
Off
S1
On
0.30
0.30
60.0
0.60
300.00
2.00
0.20
Off
20.00
30.00
20.00
30.00
20.00
30.00
20.00
30.00
Off
1.00
Off
0.30
Default
Note
Off
GRE200 (5,6)

Advertisement

loading

This manual is also suitable for:

Gr-200 seriesGr-200-6