Toshiba GR-200-5 Instruction Manual page 222

Multi functional protection ied

Advertisement

Setting of OVN_MV (Function ID: 464181)
Setting device
OVN4-DPR
OVN4-TMS
TOVN4R
ORG
OVN4
OVN4-DPR
OVN4-TMS
TOVN4R
Output
OVN4-VTFBlk
OVN4-UseFor
Range
Unit
10 - 100
% OVN4 drop-out/pick-up ratio
0.010 - 100.000
- OVN4 time multiplier (in IDMT mode)
0.0 - 300.0
s OVN4 definite time reset delay
1.0 - 220.0
V OVN4 threshold
10 - 100
% OVN4 drop-out/pick-up ratio
0.010 - 100.000
- OVN4 time multiplier (in ORG mode)
0.0 - 300.0
s OVN4 definite time reset delay
Non / Block
- OVN4 operation block by VTF
Trip / Alarm
- OVN4 used for trip or alarm
- 202 -
Contents
6F2T0207 (0.01)
Default
Note
100
1.000
0.0
120.0
100
1.000
0.0
Non
Trip
GRE200 (5,6)