Multi functional protection ied

Advertisement

Cancel logic for SBO mode
4.3.6
In the SBO control mode, the reception of a cancel command is possible in both HHD and VAR
resetting. The function will discard the select command, if the cancel has been satisfied.
Receiving "Cancel of HHD resetting" from the remote-end
(i)
Figure 4.3-11 shows the logic when a "Cancel command (Remote-Cancel)" signal is applied to
the HHD resetting. The input-point "PWRQ_HHD_RSTREQ" is the same as the "Selection
command (Remote-Reset-Control)" signal.
Input
Command "Remote-cancel"
543081 7019016D08
PWRQ_HHD_RSTREQ
Figure 4.3-11 Cancel logic by the reception of "Cancel of HHD resetting" from the remote end
†Note: The criteria "unmatched conditions" are determined when the "Test-bit status" in
the 'cancel' command is not identical to the "IED test status".
Receiving "Cancel of VAR resetting"
(ii)
Similar logic is applied. See Figure 4.3-11 by replacing "HHD" with "VAR".
Operate logic for SBO/DIR modes
4.3.7
The user should map the operation command to the operate logic for HHD and VAR resetting.
Receiving "operate command HHD resetting" from the remote-end
(i)
Figure 4.3-12 shows the logic during an "Operate command (Remote-Reset-Control)" signal is
applied in HHD resetting logic. The input-point "PWRQ_HHD_RSTREQ" is used for the
reception of the "Select command (Remote-Reset-Control)".
Input
Command "Remote-On-Control"
543081 7019016D08
PWRQ_HHD_RSTREQ
Figure 4.3-12 'HHD resetting' operation logic by the remote end
‡Note: "operate condition" signal is provided from operate condition scheme. For more
510081 7001016D08
PWRQTY function (Function ID: 543081)
Cancel command
Unmatched condition
detected†
Operate logic in PWRQTY
PWRQTY function (Function ID: 543081)
Operate Command
Operate condition‡
- 567 -
Cancel logic in PWRQTY
&
&
"HDD_RST_CMD"
(543081 8019011001)
&
Operate completed
6F2T0207 (0.01)
Output
Successes to cancel
Operation Failed
Output
All THD and TDD are reset
→ 0
I
thd
→ 0
V
thd
GRE200 (5,6)