Toshiba GR-200-5 Instruction Manual page 467

Multi functional protection ied

Advertisement

Output signal to BO
The DPSY01 function, in Figure 4.1-22, can issue an "Operate" signal at the output-point
"DPSY01_FEX_BO", when the DPSY01 function determines that the input signal "Remote-
Open-Control" is true.
Receiving "operate command Closing" from the local-end
(iii)
Figure 4.1-23 depicts the reception of the operate command 'Closing' from the local-end.
Wait for a command
Select stage
Select command Closing from the remote-end
Select command Open from the remote-end
Select command Closing from the local-end
Select command Open from the local-end
Select command Closing by the PLC function
Select command Open by the PLC function
Figure 4.1-23 Outline of operate command Closing
Input signal generated at the local-end
Figure 4.1-24 illustrates the operate logic when an "Operate command Closing (Local-Closing-
Control)" signal is applied to the DPSY01 function. The signal is generated when "Execution
of Closing" is keyed on the IED front panel.
Wait for a next command
Operate command Closing from the remote-end
Operate command Open from the remote-end
Operate command Closing l from the local-end
Operate logic
Signal reception from
the front panel
Operate command Open from the local-end
Operate command Closing by the PLC function
Operate command Open by the PLC function
- 447 -
6F2T0207 (0.01)
Success
Operation
Signal output
decision
Do nothing
Failed
GRE200 (5,6)