Download Print this page

Toshiba GR-200-5 Instruction Manual page 681

Multi functional protection ied

Advertisement

Table 5.6-5 Setting items for binary input circuits of IO#1
Setting of BIO_SLOT_MV (Function ID: 200B41)
Setting items
Common
CMP_NUM
Common for both
BITH1
BI1 and BI2
BI1
BI1_CPL
On Delay Timer
Off Delay Timer
INVERSE-SW
BI2
BI2_CPL
On Delay Timer
Off Delay Timer
INVERSE-SW
Common for
BITH2
BI3–BI15
BI3
BI3_CPL
On Delay Timer
Off Delay Timer
INVERSE-SW
BI4
BI4_CPL
On Delay Timer
Off Delay Timer
INVERSE-SW
...
....
BI15
BI15_CPL
On Delay Timer
Off Delay Timer
INVERSE-SW
Range
Unit
4 - 9
- Counting number to ignore input signals
Level_11 /
Level_12 /
Threshold level at both BI1 and BI2 of MV-BI1,
-
Level_13 /
MV-BI3, MV-BI4
Level_14
Off / On
- Switch for programming logic on binary input1
0.000 - 300.000
s Setting value for On-delay timer
0.000 - 300.000
s Setting value for Off-delay timer
Normal / Inverse
- Switch to inverse a binary input
Off / On
- Switch for programming logic on binary input2
0.000 - 300.000
s Setting value for On-delay timer
0.000 - 300.000
s Setting value for Off-delay timer
Normal / Inverse
- Switch to inverse a binary input
Level_21 /
Threshold level at BI3–BI15 of MV-BI1
Level_22 /
-
Threshold level at BI3-BI11 of MV-BI3
Level_23
Threshold level at BI3-BI10 of MV-BI4
Off / On
- Switch for programming logic on binary input3
0.000 - 300.000
s Setting value for On-delay timer
0.000 - 300.000
s Setting value for Off-delay timer
Normal / Inverse
- Switch to inverse a binary input
Off / On
- Switch for programming logic on binary input4
0.000 - 300.000
s Setting value for On-delay timer
0.000 - 300.000
s Setting value for Off-delay timer
Normal / Inverse
- Switch to inverse a binary input
....
Off / On
- Switch for programming logic on binary input15
0.000 - 300.000
s Setting value for On-delay timer
0.000 - 300.000
s Setting value for Off-delay timer
Normal / Inverse
- Switch to inverse a binary input
- 661 -
Contents
....
6F2T0207 (0.01)
Default
Note
4
Level_12
Off
0.000
0.000
Normal
Off
0.000
0.000
Normal
Level_21
Off
0.000
0.000
Normal
Off
0.000
0.000
Normal
....
Off
0.000
0.000
Normal
GRE200 (5,6)

Advertisement

loading

This manual is also suitable for:

Gr-200 seriesGr-200-6