SEF_MV (Function ID: 442081)
Setting items
ORG
SEF4
SEF4-DPR
SEF4-TMS-
ORG
SEF4-Rtimer
Rtimer
TSEF4R
SEF4-RTMS-
ORG
SEF4-k
SEF4-a
SEF4-c
SEF4-kr
SEF4-b
OUTPUT
SEF4-2fBlk
SEF4-VTFBlk
SEF4-UseFor
SEF4-ARCBlk
Range
Unit
0.001 - 1.000
A SEF4 threshold (in IDMT mode)
10 - 100
% SEF4 drop-out/pick-up ratio
0.010 - 50.000
- SEF4 time multiplier of Original inverse curve
DEF / DEP
- SEF4 reset delay type of ORG
0.00 - 300.00
s SEF4 definite time reset delay
SEF4 dependent reset time multiplier of
0.010 - 50.000
-
Original inverse curve
0.00000 - 500.00000
- SEF4 user original curve coefficient
0.00000 - 10.00000
- SEF4 user original curve coefficient
0.00000 - 10.00000
- SEF4 user original curve coefficient
0.00000 - 500.00000
- SEF4 user original curve coefficient
0.00000 - 10.00000
- SEF4 user original curve coefficient
Non / Block
- SEF4 operation block by 2f-detection
Non / Block
- SEF4 operation block by VTF
Trip / Alarm
- SEF4 used for trip or alarm
Non / Block
- Autoreclose block by SEF4
- 87 -
Contents
6F2T0207 (0.01)
Default
Note
0.010
100
1.000
DEF
0.00
1.000
0.00000
0.00000
0.00000
0.00000
0.00000
Non
Non
Trip
Block
GRE200 (5,6)