Multi functional protection ied

Advertisement

Connect PC to IED via LAN or USB
Start GR-TIEMS engineering tool
Add Substation, Voltage level, Bay and IED to the project tree
Select an IED to manage IEC61850 configuration file
Choose a required 61850 edition from the pull-down list
Import ICD/CID file from the selected IED
Map the signals to Logical Nodes
Edit Data set, RCB and GCB
Edit signals for GOOSE Publish and GOOSE Subscribe
Write configured data to IED
Figure 11.3-5 Flow diagram
(→see Chap. 11.3.3(i))
(→see Chap. 11.3.3(i))
(→see Chap. 11.3.3(ii))
(→see Chap.11.3.3(iii))
(→see Chap.11.3.3(iv))
(→see Chap. 11.3.3(iv))
(→see Chap. 11.3.3(iv))
(→see Chap.11.3.3(v))