Toshiba GR-200-5 Instruction Manual page 513

Multi functional protection ied

Advertisement

Input
Command "Local-On-Control"
ILK† condition ("ON") passed
DPOS01-Close
Either "SBO mode" or "DIR mode"
(e.g., "ctlmodel" in IEC61850*)
Figure 4.2-6 Select 'On' on the front panel in DPOS01
†Note: The ILK function provides the operation criterion for "On".
‡Note: A "select condition" signal is provided from the select condition scheme. For more
information, see Figure 4.2-13.
Note: To identify the output signals of the other DPOS logics, see Table 4.2-8.
††
Selection logic in DPOS01
DPOS01 function (Function ID: 512001)
For SBO operation
Select command
with ILK† condition
For DIR operation
Operate command
with ILK† condition
[DPOS01-CTRAHMI]
SBO
Select condition‡
- 493 -
1≥
&
&
SBO
&
DIR
††
6F2T0207 (0.01)
Output
To "Wait for a next
command"
To BO connection
"DPOS01_OSL_BO_CSF"
(512001_8603011DC6)
0
t
Select "success"
0.1s
To "Wait for a command"
t
0
Select "Failed"
0.6s
GRE200 (5,6)