Toshiba GR-200-5 Instruction Manual page 447

Multi functional protection ied

Advertisement

Receiving "select command Open" from the remote-end
(ii)
Figure 4.1-3 outlines the reception of the select command 'Open' from the remote-end.
Wait for a command
Select stage
Select command Closing from the remote-end
Select command Open from the remote-end
Signal reception
IEC61850
Select command Closing from the local-end
Select command Open from the local-end
Select command Closing by the PLC function
Select command Open by the PLC function
Input point required mapping
Figure 4.1-4 shows the select logic when a "Select command (Remote-Open-Control)" signal is
applied to the DPSY01 function. The input-point "DEV01_CONTROL_REQ" is used for the
reception of the "select command (Remote-Open-Control)" signal.
Input
Command "Remote-Open-Control"
511001_7002016D08
DEV01_CONTROL_REQ
ILK† condition ("Open") passed
DPSY01-Open
Either "SBO mode" or "DIR mode"
(e.g., "ctlmodel" in IEC61850*)
Figure 4.1-4 Select 'Open' from the remote-end in DPSY01
†Note: The ILK function can provide the operation criteria for "Open".
‡Note: A "select condition" signal is provided from the select condition scheme. For more
information, see Figure 4.1-13.
Note: To know the input and output points of the DPSY02 logic, see Table 4.1-5 and
††
Table 4.1-9.
Select logic
Figure 4.1-3 Outline of select command for Open
DPSY01 function (Function ID: 511001)
For SBO operation
Select command
with ILK† condition
For DIR operation
Operate command
with ILK† condition
For SBO operation
Select command
without ILK† condition
For DIR operation
Operate command
without ILK† condition
In SBO operate
In DIR operate
Select condition‡
Failed
Select
Signal output
decision
Success
Selection logic in DPSY01
&
&
&
&
- 427 -
6F2T0207 (0.01)
Wait for a next command
Cancel logic
Cancel command
Cancel logic
Operate logic
Operate command
Operate logic
1≥
&
To BO connection
"DPSY01_FSL_BO_FLG"
(511001 8A02011DC4)
0
t
Select "success"
0.1s
To "Wait for a command"
t
0
Select "Failed"
0.6s
††
GRE200 (5,6)
Output