Multi functional protection ied

Advertisement

Miscellaneous
Forcibly signal control function
11.8.1
When the point-to-point test is carried out, it is necessary to generate the original signal of the
transmission signal in order to confirm that the send / receive of the transmission signal is
good. However, if it will take time and effort to generate the original signal, the point-to-point
test cannot be done easily.
The forcibly signal control function is a means that the user can have the point-to-point test
easy.
Overview of the function
(i)
Figure 11.8-1 shows the scheme logic of the forcibly control function and the overview of
application.
In the case the user wants to send arbitrary signals (e.g., GOOSE messages of IEC 61850), the
user can define not to send the original signal and define to send "OUT_FSC**" instead of the
original in the forcibly signal control function. The original signals are connected to the forcibly
signal control function by using PLC logic, as Figure 11.8-1. The "OUT_FSC**" signals can be
forcibly controlled for generation / non-generation by the LCD screen.
(original) signal
connect
user want to send
using PLC
Forcibly Signal Control Function
**********
IN_FSC01
Normal
Off
FSC01-SET
On
**********
IN_FSC02
Normal
Off
FSC02-SET
On
**********
IN_FSC03
Normal
Off
FSC03-SET
On
**********
IN_FSC32
Normal
Off
FSC32-SET
On
FSC OP [ENTER]
Figure 11.8-1 Scheme logic and application
- 974 -
&
≥1
1
&
&
&
≥1
1
&
&
&
≥1
1
&
&
&
≥1
1
&
&
SIMBIT GENERATION
6F2T0207 (0.01)
OUT_FSC01
Send OUT_FSC01
instead of
original signal
OUT_FSC02
OUT_FSC03
OUT_FSC32
GRE200 (5,6)