Download Print this page

Toshiba GR-200-5 Instruction Manual page 782

Multi functional protection ied

Advertisement

Transferred information about tripped phase and mode
8.4.2
Information about the tripped phases and mode can be transferred with the signals in Table
8.4-2. For more information about tripped phases and modes, see sections 8.1.1(ii) and (iii).
Items
Number of faults recorded
Time at the fault occurrence
Fault phase A
Fault phase A
Fault phase A
Fault phase N
Relay element operated at phase A
Relay element operated at phase B
Relay element operated at phase C
Transferred state information
8.4.3
Information collected by setting [OP Mode ID*] can transferred with the signals in Table 8.4-3.
For more information about the statuses, see sections 8.1.3(i) and (ii).
Table 8.4-3 Transferred information by OP mode settings
Items
State taken by setting [OP Mode ID1]
State taken by setting [OP Mode ID2]
State taken by setting [OP Mode ID3]
....
State taken by setting [OP Mode ID128]
Logical state taken by setting [OP Mode ID201]
Logical state taken by setting [OP Mode ID202]
....
Logical state taken by setting [OP Mode ID264]
Table 8.4-2 Transferred information
- 762 -
6F2T0207 (0.01)
Signal names
FLT_CNT
FLT_TM
FLT_PH_A
FLT_PH_B
FLT_PH_C
FLT_PH_N
FLT_OP_A
FLT_OP_B
FLT_OP_C
Signal names
FLTOPM001
FLTOPM002
FLTOPM003
....
FLTOPM128
FLTOPM201
FLTOPM202
....
FLTOPM264
GRE200 (5,6)