Toshiba GR-200-5 Instruction Manual page 810

Multi functional protection ied

Advertisement

Setting
Metering settings in MES_MV (Function ID: 710081)
Setting item
Display Value
I-Display Unit
V-Display Unit
P-Display Unit
Q-Display Unit
S-Display Unit
Wh-Display Unit
varh-Display Unit
Power
Current
PF Sign
I-Valid Level
V-Valid Level
ISD
VSD
P/Q/SSD
PFSD
FSD
Wh/varhSD
PhaseSD
PeriodSD
dVSD
Demand_period
Unit
Range
s
Primary/Secondary
A/kA
V/kV
kW/MW
kvar/Mvar
kVA/MVA
kWh/MWh
kvarh/Mvarh
Send/Receive
Lead/Lag
AP/AP+RP
0.10 to 5.00
%
0.10 to 5.00
%
0.00 to 50.00
%
0.00 to 50.00
%
0.00 to 50.00
%
0.00 to 1.00
0.00 to 50.00
%
0.0 to 999.9
0.0 to 90.0
deg
0 to 4
0.00 to 50.00
%
1min / 5min /
10min / 15min /
30min / 60min
Contents
Display selection of primary or secondary
Current shown in Ampere or Kilo-Ampere
Voltage shown in Volt or Kilo-Volt
Active power shown in Kilo- or Mega-watt
Reactive power shown in Kilo- or Mega-var
Apparent power shown in Kilo- or Mega-
VA
Watt-hour shown in Kilo- or Mega-Wh
Var-hour shown in Kilo- or Mega-varh
Power flow definition (Supply or absorb)
The angle compared with the voltage
Denison of the sign of the power factor
Cutting off small entering current
Cutting off small applied voltage
Sending Dead Band in current
Sending Dead Band in voltage
P/Q/S Sending Dead Band
PF Sending Dead Band
F Sending Dead Band
Wh/varh Sending Dead Band
Phase Sending Dead Band
Period of Sending Dead band
dV Sending Dead Band
Period of demand calculation
- 790 -
6F2T0207 (0.01)
Default
Notes
setting value
Primary
kA
kV
MW
Mvar
MVA
MWh
Mvarh
Send
Lead
AP+RP
4.00
0.30
5.00
0.60
5.00
0.02
0.50
1.0
0.5
0
0.60
10min
GRE200 (5,6)