Download Print this page

Toshiba GR-200-5 Instruction Manual page 954

Multi functional protection ied

Advertisement

How to map IED signals to Modbus addresses
11.4.9
The Figure 11.4-12 is illustrated in order that an IED signal was connected for a Modbus
address, so the user has to map a Data ID for a Modbus address on the Modbus slave screen;
the operation the drag & drop on the screen. The function and data length (see Table 11.4-2) is
dependent on the Modbus address; thus, the user has to map signals based on the types of the
signals (Data IDs).
Select MODBUS tool on the Configuration tool, as shown in Figure 11.4-21; and then, the user
can edit a configuration file.
Selection of Modbus tool
Figure 11.4-21 Choice of Modbus engineering tool on GR-TIEMS
Note: We discuss the GR-TIMES operations for the Modbus mapping; hence, we use
1
some signals and addresses for the explanation of that. We omit the meanings of
applications signals.
Note: See the separate manual "
2
operation to change or erase addresses,
Operation manual GR-TIEMS (6F2M1082)
- 934 -
6F2T0207 (0.01)
" for the
GRE200 (5,6)

Advertisement

loading

This manual is also suitable for:

Gr-200 seriesGr-200-6