Download Print this page

Toshiba GR-200-5 Instruction Manual page 698

Multi functional protection ied

Advertisement

LED light up origins
(i)
LED #3 turns on when the logic get signals coming from other functions. There are eight ports:
[Input signal1] to [Input signal8]. Set a signal for the light up.
Light origins handler
(ii)
Light up signal can be generated at LED #3 logic; it will be generated using the eight origins
in a signal handler. The user can set the logic operation in the hander with setting [LOGIC-
SW]; set either AND, OR or XOR for the settings.
Delayed light-up/delayed light-off
(iii)
The user can adjust the light-up time with settings. Set the timing to light up using settings
[On Delay Timer] and [Off Delay Timer] at LED #3 logic.
Light-up inversion
(iv)
If the LED #3 should turn off when the light up signal is generated, set Inverse for the setting
[INVERSE-SW]. Normal is for non-inversion.
LED timer
(v)
LED #3 has a programmable light-off characteristic with setting [TIMER-SW]. There are five
types: (1) Instant (Off), (2) Delay, (3) Dwell, (4) Blink, and (5) Latch type:
Instant type: if the user wishes to turn off LED straightforward, when the light up signal is
reset, set Off.
Delay type: if the user requires to turn off LED with delay, set Delay for setting [TIMER-SW];
set the delay width using setting [Logic timer].
Dwell type: if required a LED lights up with one shot pulse, set Dwell for the switch [TIMER-
SW]; then, set the lighting time using setting [Logic timer]. If the arrival signal
is shorter than the setting [Logic timer], the time to LED light up will be equal
to the setting value. Conversely, if the arrival signal is longer than that of the set
value, LED light up will be equal to the length of the arrival signal.
Latch type: If required turn-off the LED with a reset signal, enter that Data ID for setting
[Reset signal] and set Latch for the switch [TIMER-SW]. Data ID may come from
other functions.
Blink type: If required blinking LED set Blink for the switch [TIMER-SW].
- 678 -
6F2T0207 (0.01)
GRE200 (5,6)

Advertisement

loading

This manual is also suitable for:

Gr-200 seriesGr-200-6