Toshiba GR-200-5 Instruction Manual page 122

Multi functional protection ied

Advertisement

OCN_MV (Function ID:443081)
Setting items
OCN1-kr
OCN1-b
Output
OCN1-2fBlk
OCN1-VTFBlk
OCN1-CTFBlk
OCN1-UseFor
OCN1-ARCBlk
OCN2
OCN2-Dir
Fwd/
OCN2-Angle
Rev
OCN2-Vpol
OCN2-Timer
DT
OCN2
OCN2-DPR
TOCN2
IEC
OCN2
OCN2-DPR
OCN2-TMS-
IEC
TOCN2R
UK
OCN2
OCN2-DPR
OCN2-TMS-
UK
TOCN2R
IEEE
OCN2
OCN2-DPR
OCN2-TMS-
IEEE
OCN2-Rtimer
TOCN2R
OCN2-RTMS-
IEEE
US
OCN2
OCN2-DPR
OCN2-TMS-US
OCN2-Rtimer
TOCN2R
OCN2-RTMS-
US
ORG
OCN2
OCN2-DPR
OCN2-TMS-
ORG
OCN2-Rtimer
TOCN2R
OCN2-RTMS-
ORG
OCN2-k
OCN2-a
Range
Unit
0.00000 - 500.00000
- OCN1 user original curve coefficient
0.00000 - 10.00000
- OCN1 user original curve coefficient
Non / Block
- OCN1 operation block by 2f-detection
Non / Block
- OCN1 operation block by VTF
Non / Block
- OCN1 operation block by CTF
Trip / Alarm
- OCN1 used for trip or alarm
Non / Block
- Autoreclose block by OCN1
NonDir / Forward /
- OCN2 directional characteristic
Reverse
-90 - 90
deg OCN2 directional characteristic angle
0.5 - 25.0
V OCN2 polarizing voltage level
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
IEEE-MI / IEEE-VI /
- OCN2 delay type
IEEE-EI / US-CO2 /
US-CO8 / Original
0.02 - 150.00
A OCN2 threshold (in DT mode)
10 - 100
% OCN2 drop-out/pick-up ratio
0.00 - 300.00
s OCN2 operating delay time
0.02 - 25.00
A OCN2 threshold (in IDMT mode)
10 - 100
% OCN2 drop-out/pick-up ratio
0.010 - 50.000
- OCN2 time multiplier of IEC inverse curve
0.00 - 300.00
s OCN2 definite time reset delay
0.02 - 25.00
A OCN2 threshold (in IDMT mode)
10 - 100
% OCN2 drop-out/pick-up ratio
0.010 - 50.000
- OCN2 time multiplier of UK inverse curve
0.00 - 300.00
s OCN2 definite time reset delay
0.02 - 25.00
A OCN2 threshold (in IDMT mode)
10 - 100
% OCN2 drop-out/pick-up ratio
0.010 - 50.000
- OCN2 time multiplier of IEEE inverse curve
DEF / DEP
- OCN2 reset delay type of IEEE
0.00 - 300.00
s OCN2 definite time reset delay
OCN2 dependent reset time multiplier of
0.010 - 50.000
-
IEEE inverse curve
0.02 - 25.00
A OCN2 threshold (in IDMT mode)
10 - 100
% OCN2 drop-out/pick-up ratio
0.010 - 50.000
- OCN2 time multiplier of US inverse curve
DEF / DEP
- OCN2 reset delay type of US
0.00 - 300.00
s OCN2 definite time reset delay
OCN2 dependent reset time multiplier of US
0.010 - 50.000
-
inverse curve
0.02 - 25.00
A OCN2 threshold (in IDMT mode)
10 - 100
% OCN2 drop-out/pick-up ratio
0.010 - 50.000
- OCN2 time multiplier of US inverse curve
DEF / DEP
- OCN2 reset delay type of ORG
0.00 - 300.00
s OCN2 definite time reset delay
OCN2 dependent reset time multiplier of ORG
0.010 - 50.000
-
inverse curve
0.00000 - 500.00000
- OCN2 user original curve coefficient
0.00000 - 10.00000
- OCN2 user original curve coefficient
- 102 -
Contents
6F2T0207 (0.01)
Default
Note
0.00000
0.00000
Non
Non
Non
Trip
Block
NonDir
-45
3.0
DT
0.40
100
1.00
0.40
100
1.000
0.00
0.40
100
1.000
0.00
0.40
100
1.000
DEF
0.00
1.000
0.40
100
1.000
DEF
0.00
1.000
0.40
100
1.000
DEF
0.00
1.000
0.00000
0.00000
GRE200 (5,6)