Download Print this page

Toshiba GR-200-5 Instruction Manual page 141

Multi functional protection ied

Advertisement

Setting
2.8.5
Setting of BCD_MV (Function ID: 452081)
Setting items
BCD-EN
BCD
BCD
TBCD
Output
BCD-2fBlk
BCD-CTFBlk
BCD-UseFor
Signal
2.8.6
Signal monitoring point
BCD_MV (Function ID: 452081)
Element ID
8000001C23
8000001B60
8000001BB0
8300001B23
8400001B62
Connection point on PLC logic
BCD_MV (Function ID: 452081)
Element ID
800000EBB0
Range
Unit
Off / On
- BCD protection scheme switch
0.10 - 1.00
- BCD relay operating value (I2/I1)
0.00 - 300.00
s BCD operating delay time
Non / Block
- BCD operation block by 2f-detection
Non / Block
- BCD operation block by CTF
Trip / Alarm
- BCD used for trip or alarm
Name
Description
BCD
BCD relay element operated
BCD-OPT
BCD protection operated
BCD_BLOCK
BCD protection block command
BCD-OPT-TRIP
Trip signal by BCD protection operation
BCD-OPT-ALARM
Alarm signal by BCD protection operation
Name
Description
BCD_BLOCK
BCD protection block command
- 121 -
Contents
6F2T0207 (0.01)
Default
Note
Off
0.20
1.00
Non
Non
Trip
GRE200 (5,6)

Advertisement

loading

This manual is also suitable for:

Gr-200 seriesGr-200-6