BI1(200B01 8001001111) for the setting [BI_ID].
4)
Set a time adjuster for the setting [SYNC ADJ]. For example, set a value (e.g., −0.050s)
for setting [SYNC ADJ]. The setting is used when the clock function should be
synchronized before reaching the 1Hz square-wave due to the propagation or the
operating time on the BI circuit.
Table 5.8-3 Setting items for the BI Time synchronization
Setting item
Range
SNTP / BI /
TimeSyncSrc
MODBUS / IRIG-B
/ IEC103
BI-SYNC
Off /On
BI_ID
[Preferred ID]
SYNC ADJ
−0.050 to +0.050
Clock
10:00
1/2
[Time]
+
2012-11-21 10:00:05
[Format]
YYYY-MM-DD HH:mm:ss
[ActiveSyncSrc]
BI
Check "BI " is shown under ActiveSyncSrc.
Figure 5.8-8 Time setting for BI
Contents
Selection of sync method
Operation of BI
Signal monitoring point
Time adjust factor (in
sec.)
- 692 -
Setting example
BI
On
200B41 8001001111
0.000
+:Delaying the clock
6F2T0207 (0.01)
Notes
−:Leading the clock
GRE200 (5,6)