Setting of UVS_MV (Function ID: 471181)
Setting device
TUVS4
IDMT
UVS4
UVS4-DPR
UVS4-TMS
TUVS4R
ORG
UVS4
UVS4-DPR
UVS4-TMS
TUVS4R
Output
UVS4-VTFBlk
UVS4-UseFor
Test setting(Function ID: 471181)
Setting device
Test option
UVS-Test
Range
Unit
0.00 - 300.00
s UVS4 operating delay time (in DT mode)
5.0 - 130.0
V UVS4 threshold
100 - 120
% UVS4 drop-out/pick-up ratio
0.010 - 100.000
- UVS4 time multiplier (in IDMT mode)
0.0 - 300.0
s UVS4 definite time reset delay
5.0 - 130.0
V UVS4 threshold
100 - 120
% UVS4 drop-out/pick-up ratio
0.010 - 100.000
- UVS4 time multiplier (in ORG mode)
0.0 - 300.0
s UVS4 definite time reset delay
Non / Block
- UVS4 operation block by VTF
Trip / Alarm
- UVS4 used for trip or alarm
Range
Unit
Off / On
- Not to execute UVS block function
- 162 -
Contents
Contents
6F2T0207 (0.01)
Default
Note
1.00
60.0
100
1.000
0.0
60.0
100
1.000
0.0
Non
Trip
Default
Note
Off
GRE200 (5,6)