Download Print this page

Toshiba GR-200-5 Instruction Manual page 245

Multi functional protection ied

Advertisement

Setting
2.20.4
VTF_MV (Function ID: 490081)
Setting items
VTF1
VTF1-EN
UVVTF
VTF2
VTF2-EN
OVGVTF
EFVTF
Range
Unit
Off / On / OPT-On
- VTF1 scheme switch
1.0 - 220.0
V Phase under voltage revel for VTF1 detection
Off / On / OPT-On
- VTF2 scheme switch
Threshold of over voltage detection in zero-
1.0 - 220.0
V
sequence phase
Threshold of over current in zero-sequence
0.10 - 150.00
A
phase to block VTF2 detection
- 225 -
Contents
6F2T0207 (0.01)
Default
Note
On
20.0
On
20.0
0.20
GRE200 (5,6)

Advertisement

loading

This manual is also suitable for:

Gr-200 seriesGr-200-6