Download Print this page

Toshiba GR-200-5 Instruction Manual page 334

Multi functional protection ied

Advertisement

Setting
2.27.4
ATO_MV (Function ID: 4C1081)
Setting items
ATO-EN
ATO-ROCOCBlk
ROCOC
ATO-ROCOC-Chara
ROCOC_ATO
T_ATO_ROCOCOFF
ATO-COM.NUM
T_ATO_Ready
T_ATO_COM1
Command
T_ATO_COM1W
-1
T_ATO_COM2
Command
T_ATO_COM2W
-2
T_ATO_COM3
Command
T_ATO_COM3W
-3
T_ATO_COM4
Command
T_ATO_COM4W
-4
T_ATO_COM5
Command
T_ATO_COM5W
-5
T_ATO_Reset
OCATO
Wide use UVATO1
Relay
UVATO2
Un
Range
it
Off / On
- ATO function use or not
Blocking or not the ATO function by ROCOC relay
Non / Block
-
operation
Rise / Down / Both - ROCOC relay character
0.05 - 5.00
A ROCOC relay operating value
0.00 - 100.00
s Prolonged time of ROCOC relay operating signal
1 / 2 / 3 / 4 / 5
- Number of ATO commands
0.00 - 300.00
s Checking time for ATO ready
0.00 - 300.00
s Output judgement time for ATO command-1
0.00 - 10.00
s Pulse width of ATO command-1
0.00 - 300.00
s Output judgement time for ATO command-2
0.00 - 10.00
s Pulse width of ATO command-2
0.00 - 300.00
s Output judgement time for ATO command-3
0.00 - 10.00
s Pulse width of ATO command-3
0.00 - 300.00
s Output judgement time for ATO command-4
0.00 - 10.00
s Pulse width of ATO command-4
0.00 - 300.00
s Output judgement time for ATO command-5
0.00 - 10.00
s Pulse width of ATO command-5
0.00 - 310.00
s ATO reset time
0.02 - 150.00
A OCATO relay operating value
5.0 - 130.0
V UVATO1 relay operating value
5.0 - 130.0
V UVATO2 relay operating value
- 314 -
6F2T0207 (0.01)
Contents
GRE200 (5,6)
Defaul
Note
t
Off
Non
Rise
1.00
0.00
1
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
10.00
5.00
50.0
50.0

Advertisement

loading

This manual is also suitable for:

Gr-200 seriesGr-200-6