Control Panel
This output operates when a zone programmed for Day Alarm is activated while the system is
disarmed and Day Alarm is turned on in the area to which this zone is allocated. The output is
reset when the Day Alarm zone is resealed or Day Alarm is turned off in the area to which this
zone is allocated or the system is armed. You can turn Day Alarm on and off by holding down
[4] or selected from the menu on KP.
0,15 Day Alarm Latching
This output operates when a zone programmed for Day Alarm is activated while the system is
disarmed and Day Alarm is turned on in area to which the zone is allocated. The output is
reset by pressing [AWAY]. You can turn Day Alarm on and off by holding down [4] or selected
from the menu on KP.
If the control panel is partitioned, you can reset only this output on the area codepad to which
the zone is allocated.
1,0 Day Alarm Enabled
This output operates when Day Alarm is enabled in any one used area. The output is reset
when Day Alarm is turned off in all used areas.
You can turn Day Alarm on and off by holding down [4] or selected from the menu on KP.
Three beeps indicate that Day Alarm is turned on, two beeps indicate that Day Alarm is turned
off.
1,1 Telephone Line Fail
This output operates when the built-in telephone line fault module detects that the telephone
line is disconnected longer than 40 sec. The output is reset when the telephone line is
restored continuously for 40 sec. This output does not operate unless Option 1 in Location
176 is selected or the function "Telephone Line Fault Indicator" (Menu 3-4-4) is enabled.
1,2 Kiss-off Received
This output operates after the control panel successfully transmitted to the receiving party, or
else the output is reset.
1,3 AUX Power Supply Fail
This output operates when the 12V SDI2 BUS devices power supply or 12V zone or output AUX
power supply fails. The output is reset when all fault AUX power supply above is reset..
1,4 AC Fail
This output operates when the AC MAINS fails. The output is reset when the AC MAINS is
restored. This output operates regardless of whether Option 2 in Location 494 is selected or
on TEXT codepad the Menu 341 "Ignore AC Fail" is enabled.
1,5 Low Battery
This output operates when a Dynamic Battery Test detects the battery failed or the battery
voltage is below 11.0 VDC. The Dynamic Battery Test is performed every 4 hours after the
system is powered up and every time the system is armed. This output is reset only after a
Dynamic Battery Test reports that the backup battery voltage is normal.
1,6 Output 1 Fail
If the Enable Monitoring of warning device option (2) in Location 492 is selected or option
"Warning Device Fault Monitor" (TEXT Codepad Menu 3-4-3) is enabled, this output operates
when the horn speaker is disconnected. The output is reset when the horn speaker is
reconnected.
1,7 Sensor Watch Alarm
This output operates when the Sensor Watch fault occurs. The output is reset when this fault
clears.
1,8 Codepad Medical Alarm
This output operates when a user activates a Codepad Medical Alarm by pressing [7] and [9]
at the same time on the remote codepad. This output is reset when a valid User Code is
entered at the remote codepad.
Bosch Security Systems, Inc.
Installation Guide
Programmable Outputs | en
2017.10 | 03 | F.01U.298.026
125