Codepad Duress Report; Codepad Panic Report; Codepad Fire Report; Codepad Medical Report - Bosch Solution 2000 Installation Manual

Hide thumbs Also See for Solution 2000:
Table of Contents

Advertisement

Control Panel
15.7.11

Codepad Duress Report

A Duress Report (Contact ID Event Code 121) is sent to the base station receiver when 9 is
added to the end of any valid User Code used to disarm the system. This alarm is always
silent. A Duress Alarm can be activated during Exit Time. In other words, if the system is
armed and then disarmed by adding 9 to the end of the User Code before Exit Time expires, a
Codepad Duress Report is transmitted. Adding 9 to the end of a User Code when arming the
system does not cause a Duress Alarm.
If you want a 3 to activate a Codepad Duress Alarm instead of 9, select Option 2 in Location
498 (refer to Consumer Options 3, page 143).
Notice!
Restore Reports are not sent for this event.
15.7.12

Codepad Panic Report

A Panic Alarm Report (Contact ID Event Code 120) is sent to the base station receiver when a
user presses either [1] and [3] or [STAY] and [AWAY] at the same time. A Panic Alarm is
audible, but you can program the alarm as silent by selecting Option 1 in Location 493 (refer
to System Options 2, page 139).
Notice!
Restore Reports are not sent for this event.
15.7.13

Codepad Fire Report

A Fire Alarm Report (Contact ID Event Code 110) is sent to the base station receiver when a
user presses [4] and [6] at the same time. A Fire Alarm is audible, but you can program the
alarm as silent by selecting Option 2 in Location 493. A distinct fire sound is emitted through
the horn speaker to indicate this type of alarm. The fire sound is different than the burglary
sound.
Restore Reports are not sent for this event.
15.7.14

Codepad Medical Report

A Medical Report (Contact ID Event Code 100) is sent to the base station receiver when a user
presses [7] and [9] at the same time. A Medical Alarm is audible, but you can program the
alarm as silent by selecting Option 4 in Location 493.
Restore Reports are not sent for this event.
15.7.15

AUX Power Supply Fail Report

A System Trouble Report (Contact ID Event Code312) is sent when either the codepad AUX
power supply is blown or the AUX power supply malfunctions. The system reports the event
approximately 10 sec after the failure.
15.7.16

AUX Power Supply Fail Restore Report

A System Trouble Restore Report (Contact ID Event Code 312) is sent when the AUX power
supply is reset. The system reports the event approximately 10 sec after power supply is
reset.
Bosch Security Systems, Inc.
Installation Guide
System Reporting Information | en
2017.10 | 03 | F.01U.298.026
115