Setting The Eco Mode - Huawei FusionPower6000 UPS5000-H-600 kVA-FT User Manual

Hide thumbs Also See for FusionPower6000 UPS5000-H-600 kVA-FT:
Table of Contents

Advertisement

UPS5000-H-600 kVA-FT(M)
User Manual (FusionPower6000)
Figure 5-7 S-ECO system status (VFD)
Figure 5-8 S-ECO system status (VI)
----End

5.3.2 Setting the ECO Mode

Prerequisites
The UPS is working in inverter mode.
Context
Issue 02 (2024-01-05)
The UPS is set to non-ECO mode by default. Set the UPS to ECO mode when
it is required.
In ECO mode, the bypass takes priority over the inverter in supplying power. If
the bypass fails, the UPS transfers to inverter mode.
Both a single UPS and a parallel system support ECO mode which ensures a
higher efficiency.
To avoid frequent transfers between ECO mode and normal mode, do not set
ECO mode when the bypass input is unstable or is sensitive to load changes.
ECO mode is not recommended when the load is less than 10%.
Before setting ECO mode, ensure that the bypass is working properly.
Copyright © Huawei Digital Power Technologies Co., Ltd.