Lead-Acid Battery Maintenance - Huawei FusionPower6000 UPS5000-H-600 kVA-FT User Manual

Hide thumbs Also See for FusionPower6000 UPS5000-H-600 kVA-FT:
Table of Contents

Advertisement

UPS5000-H-600 kVA-FT(M)
User Manual (FusionPower6000)
No.
Check Item
4
Status record

7.2 Lead-Acid Battery Maintenance

Operating Environment Checklist
No.
Check Item
1
Equipment
room
environment
2
Rodent-proof
measures
3
Installation
position
4
Ambient
temperature
Issue 02 (2024-01-05)
Acceptance Criteria
The three-phase load rate
and output power factor
are recorded.
Acceptance Criteria
● The fireproof door of
the equipment room
remains closed, and the
air conditioner works
normally without
interruption.
● There is no dust or
flammable sundries in
the equipment room.
Rodent-proof measures
are taken in the
equipment room, such as
rat guard and mouse trap.
There is no air outlet or
refrigerant copper pipe of
the air conditioner placed
above the equipment, and
no other water leakage
risks exist.
Actual temperature: ______
°C (Allowed temperature:
20°C to 30°C;
recommended
temperature: 25°C)
Copyright © Huawei Digital Power Technologies Co., Ltd.
Check Method and
Troubleshooting
● Check method: visual
inspection Check the
system status on the
LCD.
● Troubleshooting:
Equalize the three-
phase loads.
Check Method and
Troubleshooting
● Check method: visual
inspection
● Troubleshooting:
Rectify the fault based
on the acceptance
criteria.
● Check method: visual
inspection
● Troubleshooting:
Rectify the fault based
on the acceptance
criteria.
● Check method: visual
inspection
● Troubleshooting:
Rectify the fault based
on the acceptance
criteria.
● Check method:
Measure using a
hygrothermograph.
● Troubleshooting: Check
that the air conditioner
runs properly.
7 Routine Maintenance
Check
Interval
Quarterly
Check
Interval
Monthly
Monthly
Monthly
Monthly
102