LUNA2000-2.0MWH Series Smart String ESS
User Manual
Requirements on an OT or DT Terminal
●
●
●
● Do not connect aluminum wiring terminals to the terminal block. Otherwise
● Comply with the IEC 61238-1 requirements when using copper-to-aluminum
● Do not mix up the aluminum and copper sides of a copper-to-aluminum
Issue 15 (2023-11-01)
C
Crimping an OT or DT Terminal
If a copper cable is used, use copper wiring terminals.
If a copper-clad aluminum cable is used, use copper wiring terminals.
If an aluminum alloy cable is used, use copper-to-aluminum wiring terminals,
or aluminum wiring terminals along with copper-to-aluminum washers.
NO TICE
electrochemical corrosion may occur, affecting the reliability of cable
connections.
wiring terminals, or aluminum wiring terminals along with copper-to-
aluminum washers.
washer. Ensure that the aluminum side of the washer contacts the aluminum
wiring terminal, and that the copper side contacts the terminal block.
Copyright © Huawei Technologies Co., Ltd.
C Crimping an OT or DT Terminal
222