3.2 Storage Requirements

General Requirements
ESS Storage Requirements
Issue 15 (2023-11-01)
Proof that the product is stored according to the requirements must be
available, such as temperature and humidity log data, storage environment
photos, and inspection reports.
The storage environment must be clean and dry. The product must be
protected against rain and water.
The air must not contain corrosive or flammable gases.
Do not tilt the product or place it upside down.
If equipment except battery packs has been stored for more than two years, it
must be checked and tested by professionals before use.
Do not stack the ESSs.
The ground for (long-term or temporary) storage is level, and the height
tolerance of the ground in contact with the container is less than 5 mm.
The container doors are closed tightly.
Storage temperature: –40°C to +60°C; relative humidity: 5%–95% RH
Place desiccant in control unit cabins and battery cabins for long-term
storage.
The main power loop of the ESS must be disconnected during storage. It is
recommended that the auxiliary power loop be powered on to ensure that the
monitoring system works properly.