HP 3457A Service Manual page 198

Hide thumbs Also See for 3457A:
Table of Contents

Advertisement

K800 column
| must be driven low while row
| is driven high.
8-66. Contact Circuitry
Two
types
of relays
are
used
in the 44491A.
The
first
type
consists
of
relays
K800-K803
and
K806-K809
which have four normally open contacts.
These relays are used as channel relays and al-
ways have all four contacts in the same
position.
A set position exists for these relays when all four
contacts are closed and a reset position when all contacts are open.
The other type of relay used consists of K804 and K805 which have two contacts normally open and
two contacts
normally closed.
These relays are used as tree relays and when
in the set position have
contacts between
pins 10-11 and 4-5 closed and contacts between
pins 2-3 and 8-9 open.
In the reset
position, contacts are in the opposite configuration with contacts
10-11 and 4-5 open and contacts 2-3
and 4-5 closed.
Channel
relays K800-K803
along with tree relay K804 create the eight two wire channels 0-7.
When
K804 is set channels 0-3 are selected and when K804 is reset channels 4-7 are selected.
Channel relays K800-K803 along with tree relays K804 and K805 create the 4 four wire channels
10-13.
Both K804 and K805 are always set when making a four wire measurement
through channels
10-13,
Relays K808 and K809 are active when channels 8 and 9 are used as actuator channels.
When a CLOSE
command
is executed to these channels either K808 or K809 is latched in a set position connecting the
high and low input together.
Relays K806 and K807 are active when channels 8 and 9 are used to measure current,
However, a relay
protection scheme complicates operation of these relays.
When channel 8 has been selected to measure current with a CHAN or SLIST command the following
sequence of events occur:
® Relay K808 is closed which connects the high and low input together.
© Relay K806 is closed connecting the instrument's AMPS
and LO terminals to the high and
low inputs.
© Relay K808 is opened, removing the short from across the input and causing the input cur-
rent to be forced into the AMPS terminal.
K808 is used as a current shunt in this sequence so that at the time relay K806 is closed there is no
potential across the contacts.
This protects K806 from arcing, thereby, preserving the contacts.
When the channel is later opened the following sequence of events occur:
© Relay K808 is closed.
© Relay K806 is open.
®@ Relay K808 is open.
Again K808 is used as a current shunt so that when K806 is open there is virtually no potential across
the contacts.
Preservation of K806's and K807's contacts is important because low contact resistance is
required to make accurate current measurements.
HP 3457A Multimeter
8-33

Advertisement

Table of Contents
loading

Table of Contents